Downdraft Ventilators
WARNING
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer at the address
or telephone number in the warranty.
2. Before servicing or cleaning unit, switch power off at service
panel and lock the service disconnecting means to prevent
power from being switched on accidentally. When the service
disconnecting means cannot be locked, securely fasten a
prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent backdrafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and the local code au-
thorities.
5. When cutting or drilling into wall or ceiling, do not damage
electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. To reduce the risk of fire, use only metal ductwork.
8. Do not install this product with the activating switch directly
behind a burner or element. Minimum distance between the
switch and the edge of the burner should be 4 inches.
9. Loose-fitting or hanging clothing should never be worn when
operating this appliance. They may be ignited by burners/
elements on cooktop.
10.Children should not be left alone or unattended in the area
where this appliance is in use.
11. This unit must be grounded.
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
a) Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
b) Always turn hood ON when cooking at high heat or when
cooking flaming foods.
c) Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
d) Use proper pan size. Always use cookware appropriate
for the size of the surface element.
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE
EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE
FOLLOWING
a
:
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet,
or metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out immedi
ately, EVACUATE AND CALL THE FIRE DEPARTMENT.
2. NEVER PICK UP A FLAMING PAN - You may be burned.
3. DO NOT USE WATER, including wet dishcloths or towels
- a violent steam explosion will result.
4. Use an extinguisher ONLY if:
A. You know you have a Class ABC extinguisher, and you
already know how to operate it.
B. The fire is small and contained in the area where it
started.
C. The fire department is being called.
D. You can fight the fire with your back to an exit.
a
Based on “Kitchen Firesafety Tips” published by NFPA.
MODEL WIDTH BLOWER (purchase separately)
VIPR101 30" VIDV500 Interior or VEDV900 Exterior
VIPR101R 30" w/ remote control VIDV500 Interior or VEDV900 Exterior
VIPR161 36" VIDV500 Interior or VEDV900 Exterior
VIPR161R 36" w/ remote control VIDV500 Interior or VEDV900 Exterior
VIPR181 48" VIDV500 Interior, VEDV900 Exterior or VEDV1200 Exterior
VIPR181R 48" w/ remote control VIDV500 Interior, VEDV900 Exterior or VEDV1200 Exterior
WARNING - RANGETOPS ONLY: To reduce the risk of burns or ignition of clothing by reaching across burners, an "R" model
downdraft (with remote control) MUST be used with a rangetop. The remote control MUST be mounted in the countertop - at
least 4" from the burners. See "INSTALL COOKTOP" section on page 8.
!
INSTALLER:
Save this manual for Electrical
Inspector and Homeowner to use.
HOMEOWNER:
Use and Care Information on Page 11.
CAUTION
1. For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
2. To avoid motor bearing damage and noisy and/or unbal-
anced impellers, keep drywall spray, construction dust, etc.
off power unit.
3. Clean filters and grease-laden surfaces frequently.
4. Do not repair or replace any part of this appliance unless
specifically recommended in this manual. All other servicing
should be done by a qualified technician.
5. Please read specification label on product for further informa-
tion and requirements.
6. DO NOT INSTALL WITH GRILL MODEL RANGETOPS. This
will void the warranty.
7. Models VIPR101SS, VIPR161SS, and VIPR181SS (non-
remote units): DO NOT INSTALL WITH RANGETOPS. This
will void the warranty.
!
INTENDED FOR DOMESTIC COOKING ONLY
!
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - Downdraft Ventilators

1VIKING RANGE CORPORATIONDowndraft VentilatorsWARNINGREAD AND SAVE THESE INSTRUCTIONSWARNINGTO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, ORINJURY TO PE

Page 2

10Downdraft VentilatorsVIKING RANGE CORPORATIONThis page has beenleft blank intentionally.BACKSIDE OFREMOTE SWITCHTEMPLATE

Page 3 - TAKE MEASUREMENTS (CONTINUED)

11VIKING RANGE CORPORATIONDowndraft VentilatorsUSE AND CAREAlways turn the downdraft bloweron before you begin cooking toestablish an air flow in the

Page 4 - PLAN THE CABINET CUTOUTS

99042943MF20073PROFESSIONAL SERIESBUILT-IN REAR DOWNDRAFT WARRANTYONE YEAR FULL WARRANTYBuilt-in downdraft ventilators, all of their component parts a

Page 5 - Interior Blower Installation

13VIKING RANGE CORPORATIONDowndraft VentilatorsAVERTISSEMENTLIRE ET CONSERVER CES INSTRUCTIONSAFIN DE DIMINUER LES RISQUES D’INCENDIE, D’ÉLECTROCUTION

Page 6 - Exterior Blower Installation

14Downdraft VentilatorsVIKING RANGE CORPORATIONRemarque : Le débit d’air élevéde cet appareil peut affecter la flamme de certaines surfaces decuisson

Page 7

15VIKING RANGE CORPORATIONDowndraft VentilatorsSORTIEGAUCHESORTIE INFÉRIEURESORTIEDROITEPRÉPARATION DES CONDUITSInstallation du ventilateur intérieurI

Page 8

16Downdraft VentilatorsVIKING RANGE CORPORATIONPRÉPARATION DU DÉCOUPAGE DE L’ARMOIREInstallation du ventilateur intérieur Installation du ventilateur

Page 9 - TOP EDGE

17VIKING RANGE CORPORATIONDowndraft VentilatorsPRÉPARATION DU CÂBLAGEInstallation du ventilateur intérieurInstallation du ventilateur extérieur1. Le v

Page 10 - TEMPLATE

18Downdraft VentilatorsVIKING RANGE CORPORATIONACBDFPRÉPARATION DE LA HOTTEInstallation du ventilateur extérieurLa hotte est livrée sans ventilateur.

Page 11 - All Units

19VIKING RANGE CORPORATIONDowndraft Ventilators1. Découpez les trous dans l’armoire, le mur ou le plancher.2. Installez le chapeau de toit ou de mur e

Page 12 - PROFESSIONAL SERIES

2Downdraft VentilatorsVIKING RANGE CORPORATIONAIRVENTCOUNTERTOPBLOWERBOXCHIMNEY TOPCOOK TOPGEARMOTORCOVERTYPICAL INSTALLATION120 VACGROUNDEDOUTLETThis

Page 13 - Ventilateurs encastrés

20Downdraft VentilatorsVIKING RANGE CORPORATIONCÂBLAGE ÉLECTRIQUEInstallation du ventilateur intérieur1. Installez une boîte électrique standard avec

Page 14 - Tous les appareils

21VIKING RANGE CORPORATIONDowndraft VentilatorsINSTALLATION DE LA TÉLÉCOMMANDE1. À l’aide du gabarit ci-dessous, tracez les 3 trous sur lecomptoir. Ma

Page 15

22Downdraft VentilatorsVIKING RANGE CORPORATIONVentilateurs encastrésCette page a été laisséeen blanc volontairement.ARRIÈRE DU GABARIT DELA TÉLÉCOMMA

Page 16 - 5½"

23VIKING RANGE CORPORATIONDowndraft VentilatorsUTILISATION ET ENTRETIENActionnez toujours la hotte encas-trée avant de commencer à cuisinerafin de cré

Page 17 - PRÉPARATION DE LA HOTTE

F20073GARANTIE DES HOTTES ENCASTRÉES DE SÉRIE PROFESSIONNELLEGARANTIE COMPLÈTE D’UN ANLes ventilateurs encastrés, ainsi que toutes leurs pièces et acc

Page 18 - Tous les modèles

3VIKING RANGE CORPORATIONDowndraft Ventilators1. The interiordowndraft blowersystem is designedfor use with 3-1/4" x10" ductwork (can betran

Page 19

4Downdraft VentilatorsVIKING RANGE CORPORATIONPLAN THE CABINET CUTOUTSInterior Blower Installation Exterior Blower InstallationCENTER LINEOF COUNTERCU

Page 20

5VIKING RANGE CORPORATIONDowndraft VentilatorsPLAN THE WIRINGInterior Blower Installation Exterior Blower Installation1. The Exterior Downdraft Blower

Page 21 - BORD DU COMPTOIR

6Downdraft VentilatorsVIKING RANGE CORPORATIONPREPARE THE DOWNDRAFTExterior Blower InstallationThe downdraft is shipped without a blower. Purchase a M

Page 22 - LA TÉLÉCOMMANDE

7VIKING RANGE CORPORATIONDowndraft Ventilators1. Cut hole in cabinet as well as holes in wall or floor asnecessary.2. Mount the roof or wall cap and w

Page 23

8Downdraft VentilatorsVIKING RANGE CORPORATIONINSTALL ELECTRICAL WIRINGInterior Blower Installation1. Mount a standard wiring box, with 3-pronged rece

Page 24

9VIKING RANGE CORPORATIONDowndraft VentilatorsINSTALLATION OF REMOTE CONTROL SWITCH1. Using the template below, lay out the 3-hole pattern on thecount