TECHNICAL DATA
March 28, 2013
Dry 120a
DRY VALVE
MODEL F-1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
The Viking Model F-1 Dry Pipe Valve is a latching differential valve used to separate the water
supply from the dry pipe sprinkler system. The valve combines a positive latching clapper and
air plate assembly with a differential air-to-water seat design. The latching clapper and air plate
assembly provides a positive mechanical seal for the air pressure in the dry pipe system. The
differential design allows an air supply of moderate pressure to control a higher water supply
pressure. When the air pressure in the dry pipe system is lowered sufciently to destroy the
pressure differential, the valve opens allowing water to enter the dry pipe system.
The valve is also designed to operate a water motor alarm and/or an electric pressure alarm
switch. The Viking Model D-2 or E-1 Accelerator can be used to speed the operation of the valve
on large capacity systems or where faster action is required.
2. LISTINGS AND APPROVALS
cULus Listed: VPZV
FM Approved: Dry Pipe Valves
NYC Department of Buildings: MEA 89-92-E, Vol. 22
LPCB Approved
CE Certied: Standard EN 12259-3, EC-certicate of conformity 0832-CPD-2011
VdS Approved: Certicate G4980057 - 3”, G4960044 - 4”, and G4960055 - 6”
3. TECHNICAL DATA
Specifications:
Rated to - 175 PSI (12.1 bar) Water Working Pressure.
Factory tested hydrostatically - 350 PSI (24.1 bar) with the clapper open.
Air pressure to water pressure area differential: Approximately 6 to 1.
Color - Red
Form No. F_070392
DESCRIPTION
NOMINAL
SIZE
PART
NO.
FRICTION
LOSS*
C
v
FACTOR
SHIPPING
WEIGHT
Flange / Flange
Flange Drilling
ANSI 3" 09441
3 ft.
(0.91 m)
800
130 lbs.
(59 kg)
ANSI 4" 07628
5 ft.
(1.52 m)
821
130 lbs.
(59 kg)
ANSI 6" 08464
49 ft.
(14.9 m)
780
197 lbs.
(89 kg)
PN10/16 DN80 09969
3 ft.
(0.91 m)
800
130 lbs.
(59 kg)
PN10/16 DN100 08841
5 ft.
(1.52 m)
821
130 lbs.
(59 kg)
PN10/16 DN150 08464
49 ft.
(14.9 m)
780
197 lbs.
(89 kg)
* Expressed in equivalent length of Schedule 40 pipe based on Hazen & Williams
formula: C = 120.
Table 1
DESCRIPTION
NOMINAL
SIZE
PART
NO.
FRICTION
LOSS*
C
v
FACTOR
SHIPPING
WEIGHT
Flange / Groove
Flange Drilling / Pipe O.D.
ANSI / 89 mm 3" 09446
3 ft.
(0.91 m)
800
125 lbs.
(57 kg)
ANSI / 114 mm 4" 07627
5 ft.
(1.52 m)
821
125 lbs.
(57 kg)
ANSI / 165 mm 6" 12654
49 ft.
(14.9 m)
780
184 lbs.
(84 kg)
ANSI / 168 mm 6" 08491
49 ft.
(14.9 m)
780
184 lbs.
(84 kg)
PN10/16 / 89 mm DN80 09970
3 ft.
(0.91 m)
800
125 lbs.
(57 kg)
PN10/16 / 114 mm DN100 09538
5 ft.
(1.52 m)
821
125 lbs.
(57 kg)
PN10/16 / 165 mm DN150 12653
49 ft.
(14.9 m)
780
184 lbs.
(84 kg)
PN10/16 / 168 mm DN150 08491
49 ft.
(14.9 m)
780
184 lbs.
(84 kg)
* Expressed in equivalent length of Schedule 40 pipe based on Hazen & Williams
formula: C = 120.
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Q= C
v
P
S
Q = Flow
C
v
= Flow Factor (GPM/1 PSI ∆P)
∆P = Pressure Loss through Valve
S = Specic Gravity of Fluid
Revised page replaces page 120a-k, dated February 25, 2011.
(Added VdS approvals)
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - TECHNICAL DATA

TECHNICAL DATAMarch 28, 2013Dry 120aDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 2

TECHNICAL DATAMarch 28, 2013Dry 120jDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 3

TECHNICAL DATAMarch 28, 2013Dry 120kDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 4

THIS PAGE INTENTIONALLY LEFT BLANKForm No. F_070392Revised page replaces page 120a-k, dated February 25, 2011. (Added VdS approvals)

Page 5

TECHNICAL DATAMarch 28, 2013Dry 120bDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 6

TECHNICAL DATAMarch 28, 2013Dry 120cDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 7

TECHNICAL DATAMarch 28, 2013Dry 120dDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 8

TECHNICAL DATAMarch 28, 2013Dry 120eDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 9

TECHNICAL DATAMarch 28, 2013Dry 120fDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 10

TECHNICAL DATAMarch 28, 2013Dry 120gDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 11

TECHNICAL DATAMarch 28, 2013Dry 120hDRY VALVEMODEL F-1The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 T

Page 12 - LEFT BLANK